Project Description
24/33/110/126/132kV SF6 (Vacuum) Circuit Breaker
Description:
LW36 model is outdoor SF6 (Vacuum) circuit breaker using sulfur hexafluoride gas or vacuum as the arc extinguishing and insulating medium and adopts the most advanced self-energy arc-extinguishing technology. It has the characteristics of long electrical life, low operating power and high reliability.
Guaranteed Technical Parameters
Description |
Unit | Guaranteed Values | |||
Rated voltage | kV | 24 | 36 | 40.5 | |
Rated insulation level | Lightning impulse withstand voltage (full wave peak) |
kV | 150 | 170 | 210*/215 (fracture) 185 |
Power frequency withstand voltage (1 minute) |
kV | 65 | 75 | 95 | |
Rated current | A | 1250/1600/2000/2500 | |||
Mechanical life | Operations | 10000 | |||
SF6 gas rated pressure (25 gauge pressure) | MPa | 0.45 | |||
Blocking pressure (time gauge pressure) | MPa | 0.40 | |||
Maximum 4 ℃ ambient temperature | ℃ | -30 | |||
Rated short circuit breaking current | kA | 20/25/31.5/40 | |||
Rated short circuit making current (peak value) | kA | 50/63/80/100 | |||
Rated short time withstand current (thermal stability current) | kA | 20/25/31.5/40 | |||
Rated peak withstand current (dynamic stability current) | kA | 50/63/80/100 | |||
Rated out of step breaking current | kA | 50/63/80/100 | |||
Rated short circuit duration | s | 4 | |||
Closing time (at rated operating voltage) | ms | ≤80 | ≤80 | ≤100 | |
Opening time (under rated operating voltage) | ms | ≤65 | ≤65 | ≤70 | |
Rated operating sequence |
0-0.3s-CO-180s-CO |
||||
Rated switching current of single capacitor bank | A | 400 | |||
Annual air leakage rate | %/year | ≤1 | |||
Water content of SF6 gas (at 20 ℃) | ppm (V/V) | ≤150 | |||
Rated operating voltage of CT14 spring operating mechanism | V | DC: 110, 220 AC; 110, 220, 380 | |||
Closing coil and breaking coil voltage | V | DC: 110, 220 AC; 110, 220, 380 | |||
Voltage of energy storage motor | V | AC: 220, DC: 220 | |||
Closing speed | m/s | 3.2 ± 0.2 | 3.2 ± 0.2 | 3.2 ± 0.2 | |
Opening speed | m/s | 3.4±0.2 | 3.4±0.2 | 3.4±0.2 | |
Weight of sulfur hexafluoride gas | kg | 7-8 | |||
Weight of circuit breaker (including operating mechanism) | kg | 800/900/1400 |
No. |
Description of Parameters | Unit |
Value |
|
1 |
Rated voltage |
KV |
126 |
|
2 |
Rated current |
A |
3150 |
|
3 |
Rated frequency |
HZ |
50 |
|
4 |
First pole to clear factor |
1.5 |
||
5 |
Rated short circuit breaking current |
KA |
40 |
|
6 |
Rated short-circuit current (peak) |
KA |
100 |
|
7 |
Rated short-circuit withstand current |
KA |
40 |
|
8 |
Rated power frequency withstand voltage (1min) | Phase to earth |
KV |
K·230 |
Phase to phase |
K·(230+70) |
|||
9 |
Rated lightning impulse withstand voltage | Phase to earth |
KV |
K·550 |
Phase to phase |
K·(550+103) |
|||
10 |
Rated peak withstand current |
KA |
100 |
|
11 |
Rated out of step current |
KA |
10 |
|
12 |
Close fault current |
KA |
90%1K |
|
13 |
Electrical life of rated short circuit breaking current |
times |
20 |
|
14 |
Rated short circuit duration |
s |
4 |
|
15 |
Rated line charging close current |
A |
31.5 |
|
16 |
Rated operation sequence |
O-0.3s-CO-180s-CO35 |
||
17 |
Main circuit resistance |
μΩ |
≤35 |
|
18 |
Rated SF6 gas pressure |
MPa |
0.6 |
|
19 |
SF6 gas leakage rate |
ppm |
≤0.55 |
|
20 |
Moisture content of SF6 gas (V/V) |
|
≤150 |
|
21 |
Mechanical life |
times |
10000 |
|
22 |
Electric distance | Phase to earth |
mm |
3906/3150 |
Phase to phase |
3906/3150 |
|||
23 |
Each filled with SF6 gas quality |
kg |
8 |
|
24 |
Quality of each circuit breaker |
kg |
~ 1700 |